Emergency led driver battery installation scheme output power 3W1.5 hours

KVD188C
Emergency Conversion Kits apply in Led constant current lighting luminaires’ normal lighting or emergency lighting mode, also can be only for emergency lighting purposes.

Emergency lighting solutions provided “charging”, and “discharging” functions, and use intelligent IC controlling circuits, according to be high exchange efficiency and smaller battery capacity.

Internal Li-ion battery, compatible with dimming or non-dimming led luminaire, external installation, emergency supply will be standing and charging by when AC grid electricity supply in normal, will be going to self-maintenance when fully charged, according to longer the battery’s lifespan

The emergency driver will be back up the lighting luminaires within 1 second when AC grid electricity stopped, to be sure the light can be working for 1 to 3hrs normally.

Model: KVD188C LED emergency conversion kit, built-in one  2000mah lithium-ion battery, this emergency conversion kit can be used for lights with maximum 100W external LED drivers,
So it is a perfect LED emergency conversion kit for LED panel lights, ceiling lights, downlight, and tri-proof lights.
The maximum driving current of LED lamps cannot exceed 2.5A. the maximum DC voltage of the lamp board does not exceed 85V。

Emergency led driver Conversion Kits specifications:
1. Emergency Power: 3W 5W
2. Lighting fixture Power: 10W-100w
3. Conversion Efficiency: ≥95%
4. Battery Type: 1 pcs Li-ion battery inside
5. Emergency runtime : 3w and 1.5 hours  with 2000 mAh Li-ion battery or 5w and 3 hours with 5000 mAh Li-ion battery
6. Input Voltage: AC220-240V
7. Output Voltage: DC10V-85V  (DC30-165V  needs to be Customized )
8. Charging Time: 24 hours
9. Product Weight: 2000mAh Li-ion battery-230g   5000mAh Li-ion battery-300g
10. Working Lifetime(Hour)30000
11. 3 years warranty.
12. Best quality and factory price.
13. Obtain CE ROHS UKCA  CB from TUV

Emergency Ballast  Advantages:
Lighting emergency products
Obtained CE ,UKCA,TUV-CB certifications
Comply CE ,UKCA ordinances, and TUV-CB
Compatible with all brands of constant current LED drivers
Constant power outpus
High voltage output
Low energy consumption complies with CEC standards
Charging and dis-charging protection function and over heat temp. protection
Battery zero power consumption under static state
Mock-up electricity pause emergency testing function
Can be power off under emergency status
Indication light: city grid electricity,charging, fault
Seasonal self detect function
Protection functions: over voltage, short circuit, over load and open circuit
Metal housing, comply EMC, FCC and C tick ordinances
IP grade: IP20
We obtained international air and sea transportation documents

Working & storage temperature: 0℃–+50℃(Standard temperature  20℃-35℃ is best )
To ensure a longer lifetime, LED emergency battery is needed to be charged and discharged every 3 months.
If stored longer than 3 months in a warehouse, emergency battery is needed to be charged and discharged every 3 months.
Our emergency batteries can be charged/discharged 500 cycles if used in a right way.
Please make sure wire connection is correct before switch on for a long time usage